25mm2
Implementation according to PN-E/90081
Conductor construction | Calculated cross section | Overall diameter | Conductor weight | Calculated breaking load | Calculated dc resistance at 20°C |
---|---|---|---|---|---|
mm | mm2 | mm | kg/km | kN | ohm/km |
7/2,13 | 24,94 | 6,39 | 226 | 8,60 | 0,7361 |
70mm2
Implementation according to PN-E/90081
Conductor construction | Calculated cross section | Overall diameter | Conductor weight | Calculated breaking load | Calculated dc resistance at 20°C |
---|---|---|---|---|---|
mm | mm2 | mm | kg/km | kN | ohm/km |
19/2,17 | 70,27 | 10,85 | 637 | 24,22 | 0,2613 |
95mm2
Implementation according to PN-E/90081
Conductor construction | Calculated cross section | Overall diameter | Conductor weight | Calculated breaking load | Calculated dc resistance at 20°C |
---|---|---|---|---|---|
mm | mm2 | mm | kg/km | kN | ohm/km |
19/2,52 | 94,76 | 12,60 | 859 | 32,67 | 0,1938 |
185mm2
Implementation according to PN-E/90081
Conductor construction | Calculated cross section | Overall diameter | Conductor weight | Calculated breaking load | Calculated dc resistance at 20°C |
---|---|---|---|---|---|
mm | mm2 | mm | kg/km | kN | ohm/km |
37/2,52 | 184,50 | 17,64 | 1673 | 63,30 | 0,0995 |